A fire log book is where a care home shows that its fire precautions are being checked, tested and fixed. When a fire officer visits, or an inspector asks how you know the building is safe, it is one of the records they are likely to ask to see.
This guide covers what the law says about fire records, what government guidance for residential care premises suggests you check and how often, and what a useful entry looks like. It is written for registered managers of care homes and supported living services in England, with a short note on the other nations at the end.
Is a fire log book a legal requirement?
Not by that name. No law says "you must keep a fire log book". But the law does require records, and a log book is the usual way to keep them.
In England and Wales, fire safety in care homes falls under the Regulatory Reform (Fire Safety) Order 2005, often called the Fire Safety Order. It places the duties on the "responsible person", which in a care home is normally the provider or whoever has control of the premises.
Three duties matter most for record keeping:
- The responsible person must make a "suitable and sufficient assessment" of fire risk (article 9).
- Facilities, equipment and devices provided for fire safety must be "subject to a suitable system of maintenance" and kept in efficient working order (article 17).
- Staff must be given adequate fire safety training, repeated as needed (article 21).
The rules on recording the fire risk assessment changed on 1 October 2023. Before that date, the duty to record "significant findings" only applied in some cases, such as where five or more people were employed or the premises were licensed. Section 156 of the Building Safety Act 2022 changed article 9, and the Home Office now says every responsible person must record the fire risk assessment in full, including all the findings, and their fire safety arrangements. If someone else helps you complete the assessment, you must record their name and, where relevant, their organisation.
The government guide for care homes, "Fire safety risk assessment: residential care premises", was written before that change, so its wording about who must record findings is out of date. Its advice on checks, drills and records still stands, and it is direct about log books: "You may find it useful to keep a log book of all maintenance and testing." It also says there is no "correct" format. A log book, paper or digital, is simply how most homes prove the checks happened.
Who enforces fire safety in a care home?
The Fire Safety Order is enforced by the fire and rescue authority for your area. The residential care guide says your fire safety documentation "should be available for inspection by representatives of the enforcing authority."
CQC does not enforce the Fire Safety Order, but fire safety is still part of its regulations. Regulation 12 of the Health and Social Care Act 2008 (Regulated Activities) Regulations 2014 requires providers to make sure their premises are "safe to use for their intended purpose". Regulation 15 requires premises and equipment to be clean, secure, suitable and "properly maintained". Under the Safe key question, CQC's Safe environments quality statement says: "We detect and control potential risks in the care environment." CQC lists premises, "including gas, electrical and fire safety", among the topics it covers, and names the Fire Safety Order as related legislation.
An inspector may ask how you know the fire alarm works or when you last ran a drill. An up-to-date log book answers quickly. See our guide on how to prepare for a CQC inspection.
What should a fire log book contain?
The residential care guide lists what fire safety records could include. Put simply, the log book should cover:
- the findings of your fire risk assessment and the action taken on each one
- checks of escape routes and final exit locks, including panic devices and electromagnetic door releases
- weekly fire alarm tests and periodic servicing by a competent person
- false alarms
- emergency lighting tests and servicing
- fire extinguisher, fire blanket and hose reel checks and servicing
- any other fire systems, such as sprinklers or smoke control, and their maintenance
- fire doors and other passive fire protection
- fire safety training for staff
- fire drills and evacuation exercises
- alterations, repairs and maintenance of fire safety systems
- near misses, lessons learned and the remedial action taken
The guide also suggests recording who carries out inspections and tests, and their competence. Keep your fire risk assessment, emergency plan and contractor certificates with the log book, or clearly cross-referenced.
How often should fire checks be done?
The residential care guide gives examples of checks and how often to do them. It says these examples are "not intended to be prescriptive", so your fire risk assessment and your contractor may set a different routine. Here is what the guide suggests.
Daily checks
- Escape routes and exits are clear, and doors on them swing freely and close fully.
- Security devices on fire exits do not stop people escaping.
- The fire alarm panel shows the system is active and working.
- Emergency lighting units look in good repair, and safety signs can be read.
- Corridor fire doors are closed at night under a set routine.
Weekly checks
- Test the fire alarm and manual call points, following the manufacturer's or installer's instructions. The guide says it is good practice to test at the same time each week, with extra tests so staff on different shifts hear the alarm.
- Check that extinguishers and hose reels are in place and look in working order.
Monthly checks
- Test emergency lighting. The guide describes a monthly function test that makes sure each emergency lamp lights.
- Check that fire doors work and close properly, and that frames and seals are intact.
- Check fire extinguishers. The guide says a monthly check should be enough in normal conditions.
Six-monthly checks
- A competent person should test and maintain the emergency lighting and the fire detection and warning system. For fire alarms, the guide says this is usually done under a service contract with a specialist company and points to British Standard BS 5839-1.
Annual checks
- A competent person should test and maintain all firefighting equipment, fire alarms and other installed systems.
- Emergency lighting gets a full discharge test. The guide warns batteries typically take 24 hours to recharge, so plan the test and cover arrangements carefully in a home where people sleep.
- Extinguishers are maintained by a competent person, with guidance in BS 5306-3.
- Fire doors and other fire compartmentation are inspected and repairs made.
British Standards are revised over time, and the guide cites the editions current when it was written. Ask your fire alarm and emergency lighting contractors which current standard they service to, and note it in the log book.
What a good log entry looks like
Every entry should let someone who wasn't there understand what happened. Record:
- the date and time
- what was checked or tested, and where (for example, the call point or zone used)
- the result: working, or the fault found
- the action taken, or the action needed and who is responsible
- the date the fault was fixed
- the name of the person who did the check
The "fixed" date is easy to leave out, and a log of faults with no sign they were sorted shows a problem was known and not acted on. The guide notes the quality of records "may also be regarded as a good indicator" of how well safety is managed.
Fire drills: what to log
The guide says a fire drill should be carried out "at least annually or as determined by your fire risk assessment", and more often if you have high staff turnover. It also says it is advisable to either have one drill at night or to simulate night-time conditions, including night staffing levels.
Night-time matters in care homes. The guide says your risk assessment should identify how many staff you need to carry out your emergency plan, and that you should be able to show you always have enough staff to do it without outside help. A drill run with night staffing levels is one way to show that.
For each drill, log:
- the date, time, and whether it was a day or night (or simulated night) drill
- the scenario, including which exit or route was treated as blocked
- who took part, including staff numbers on duty and whether residents were involved
- which call point was used to raise the alarm
- whether the alarm receiving centre was told before and after, if your system is monitored
- how long it took to move people to a place of safety
- the roll call result and anyone unaccounted for
- problems seen, such as doors that were hard to open, people heading for lifts, or delays moving residents who need help
- the debrief, the actions agreed, who owns each one and when it was done
The guide suggests a different call point and blocked route at each drill, nominated observers, and including regular respite residents in some drills. It cautions that surprise drills may bring risks that outweigh the benefits.
Evacuation strategy, PEEPs and the log book
Most care homes cannot get everyone straight outside at once. The guide says that, apart from small premises where residents can escape quickly without help, care premises it covers "should develop a strategy of progressive horizontal evacuation". That means moving residents through fire-resisting doors into a protected area on the same floor, and moving them further only if needed.
The guide says the number of beds in each protected area should depend on the minimum number of staff awake and available, normally the night-time staffing level. Drills are where you test whether that works.
Some residents need their own plan. The guide says personal emergency evacuation plans (PEEPs) may need to be considered and may need to be included in the resident's care plan. When a drill shows a PEEP no longer works, log it and update the plan. Our guide to PEEPs in care homes covers how to write and review them.
Fire training records
The guide says fire safety training should take account of your fire risk assessment, happen during working hours, be "repeated periodically where appropriate", and be given to new, agency and temporary staff before they start. Its checklist asks whether you are "maintaining a record of training sessions".
Your records should show who was trained, when, what it covered and when it is next due, including agency staff and the extra training for fire wardens. See our guide to mandatory training for care home staff for how fire training fits with the rest.
Contractor servicing records
For each contractor visit, keep:
- the date, company and engineer's name
- what was serviced, such as the fire alarm, emergency lighting, extinguishers or sprinklers
- the certificate or report, and the standard worked to
- any defects found, with the date each was put right
The guide says third-party certification is one way to get assurance of a contractor's competence, and that a competent maintenance contractor can advise on what records to complete.
Common mistakes
- Gaps in the weekly alarm test around holidays or staff changes.
- Faults logged with no repair date.
- Drills only ever held in the daytime, with day staffing.
- No note of which call point was tested.
- Contractor certificates kept in an inbox, away from the log.
- Training records that miss agency or bank staff.
- A fire risk assessment not reviewed after building work or changes in residents' needs.
- PEEPs that don't match what happened in the last drill.
What good looks like
A good fire log book is boring to read. Every week has an alarm test, every fault has a fix date, drills cover day and night conditions, and contractor certificates are attached. A new manager or a fire officer could understand the state of the building in ten minutes.
Fire records are also part of good governance. See our guides to CQC Regulation 17 and the care home policies and procedures list, which includes the fire policy your log book supports.
Keeping it digital
Kiwi records fire checks and fire drills for each home, keeps fire documents with them, runs custom fire audits with photo evidence, and produces a fire log book PDF from those records. Kiwi doesn't replace your fire risk assessment. See how fire safety works in Kiwi.
Printable fire log checklist
Use this as a quick check of your own log book:
- Fire risk assessment recorded in full, in date, with the assessor named, and its actions tracked
- Emergency plan and evacuation strategy on file
- Daily escape route and fire panel checks
- Weekly fire alarm test, with call point and result
- Monthly emergency lighting, fire door and extinguisher checks
- Six-monthly fire alarm and emergency lighting servicing certificates
- Annual extinguisher servicing and emergency lighting full discharge test
- Fire drills logged, including a night or simulated night drill, with actions completed
- PEEPs in place and reviewed after drills
- Fire training recorded for all staff, including agency and bank staff
- False alarms, faults, repairs and alterations recorded with dates
- Contractor names, competence and certificates
Wales, Scotland and Northern Ireland
Wales: the Fire Safety Order also applies in Wales, so the duties above apply. The section 156 recording changes came into force in Wales on the same date, 1 October 2023.
Scotland: care homes come under the Fire (Scotland) Act 2005, and the Scottish Government publishes its own practical fire safety guidance for existing care homes. Use that instead of the English guide.
Northern Ireland: care homes come under the Fire and Rescue Services (Northern Ireland) Order 2006 and the Fire Safety Regulations (Northern Ireland) 2010. Use Northern Ireland guidance instead of the English guide.
Frequently asked
Is a fire log book a legal requirement for care homes?
Not by name. The law in England and Wales requires a recorded fire risk assessment, recorded fire safety arrangements, maintained fire equipment and trained staff. Government guidance suggests a log book as a useful way to record tests and maintenance.
How often should the fire alarm be tested in a care home?
The government guide for residential care premises suggests testing the fire alarm weekly, ideally at the same time each week, with servicing by a competent person every six months.
How often should care homes do fire drills?
The guide says at least annually or as your fire risk assessment determines, and more often if staff turnover is high. It advises one drill at night or under simulated night-time conditions.
What should a fire drill record include?
The date and time, the scenario, staff on duty, residents involved, the call point used, evacuation time, roll call result, problems found, and the actions agreed and completed.
Who is responsible for the fire log book?
The responsible person under the Fire Safety Order, usually the provider. Day-to-day checks are often delegated to the registered manager or a nominated person, but the legal duty stays with the responsible person.
Sources
- The Regulatory Reform (Fire Safety) Order 2005, article 9 (risk assessment). legislation.gov.uk
- The Regulatory Reform (Fire Safety) Order 2005, article 17 (maintenance). legislation.gov.uk
- The Regulatory Reform (Fire Safety) Order 2005, article 21 (training). legislation.gov.uk
- The Regulatory Reform (Fire Safety) Order 2005, article 25 (enforcing authorities). legislation.gov.uk
- Check your fire safety responsibilities under Section 156 of the Building Safety Act 2022. Home Office, GOV.UK
- Fire safety risk assessment: residential care premises. HM Government / Home Office, GOV.UK (published 2006, page updated 12 Sep 2023)
- The Health and Social Care Act 2008 (Regulated Activities) Regulations 2014, regulation 12. legislation.gov.uk
- The Health and Social Care Act 2008 (Regulated Activities) Regulations 2014, regulation 15. legislation.gov.uk
- Safe environments (quality statement). Care Quality Commission
- The Building Safety Act 2022 (Commencement No. 3, Transitional and Saving Provisions) (Wales) Regulations 2023, regulation 3. legislation.gov.uk
- The Fire and Rescue Services (Northern Ireland) Order 2006. legislation.gov.uk
- The Fire Safety Regulations (Northern Ireland) 2010. legislation.gov.uk
- Fire safety - existing care homes: practical guidance. Scottish Government, gov.scot